The kW of a resistive load bank is “real” power in electrical terms. When a resistive AC load bank is used to test an engine generator set the engine will produce its full horsepower rating, dissipate engine exhaust gases, and produce thermal energy into the engine cooling system. The resistive load bank in fact, will completely test the engine and its various systems.

It is important to understand that the generator or power system will not be loaded to its full kVA rating. Resistive load banks utilize resistors, which only provide kW loading at 1.0 (unity) power factor.

Description

Below is specification for some common models, we build more than these. Please contact Kongter to specify your customized model if you could not find the same model below.

ModelsR-6kW-AC220VR-30kW-AC380VR-60kW-AC380VR-100kW-AC380VR-200kW-AC380VR-500kW-AC380V
Capacity:6kW30kW 60kW100kW200kW400kW 
Rated Voltage:AC220V±10%Three Phase AC380V/400V±10%
Rated Current:1P:27.2A1P:45.5A
3P:136.5A
1P:91A
3P:272.7A
1P:151.5A
3P:454.5A
1P:303A
3P:909A
1P:608A
3P:1824A
Frequency:50Hz/60Hz50Hz/60Hz50Hz/60Hz50Hz/60Hz50Hz/60Hz50Hz/60Hz
Power Factor:PF=1.0
Minimum Load Step:100W100W100W1kW1kW10kW
Display:Voltage, Current, Frequency, Power and PF displayed on digital meter
Protection:Overheat alarm, Overheat protection, Short circuit protection, Over/Low voltage protection, Over current protection & Emergency stop button.
Control Mode:Manual control by MCBs or push buttons per customer’s choice
Air Flow:Horizontal, Force-air cooling
Dimension:49*60*21(cm)50*67*116(cm)51*97*110(cm)51*97*155(cm)80*120*161(cm)  80*180*150(cm)     
Options:Handle panel or PC remote control 
  • Compact load bank unit with user friendly control panel.
  • Effectively applied for full load test of generator set, UPS and other AC power systems.
  • Sectionalized control of input power enables any customized setting of load step and time.
  • Real-time display of test current, voltage, power, power factor, time and frequency.
  • Alternative control modes by local control of circuit breaker/push button or PC control.
  • PC software com protocol is open for data integration to customer’s IT system.
  • Emergency stop button for quick termination of AC load test.
  • Protection upon over load, over voltage, over temperature, short circuit and so on.
  • It adopts latest load element with high density power, safer and more durable.
  • Axial flow fans with big blast capacity for quick ventilation with low noise.
  • Many more customized models (resistive, inductive, capacitive or combined) available upon request
  • Battery bank system
  • Energy storage system
  • Energy meter loop load test
  • Datacenter rack heat simulating
  • PV system Inverter anti-islanding test
  • Voltage regulator, rectifier aging load test
  • Genset, UPS load bank commission testing
  • AC/DC power supply, power source commission acceptance test 

Standard Protections:

  • Emergency stop operation: one key stop loading
  • Over temperature alarm/protection: alarm & remove load
  • Fan interlock protection: loading available after fan activated
  • Over voltage protection: alarm & remove load

Optional Protections:

  • Blower thermal overload protection: alarm & remove load
  • Lack of air volume protection: alarm & remove load
  • Short circuit protection by fuse(over current protection)
  • Phase sequence protection(for fans with 3 phase voltage)
  • Air inlet & outlet temperature monitoring
  • Or other functions as requested

Control Modes:
Two control modes available for Kongter’s series AC load banks via local panel and PC software.

  • Local control mode by contactor or circuit breaker as requested by customer
  • PC software control (optional)
    Communication protocol of PC software is open to users for integration to their own system. 