Home / PM-32 Multifunction Power Meter

Products

PM-32 Multifunction Power Meter

PM-32 is a powerful multifunction power meter that measures more than 60 parameters such as P, Q, cosΦ, F, kWh, kvarh, etc.
The standard PM-32 has RS-485 communication protocol, 2 energy pulse outputs (active and reactive each) functions.
With optional modules, PM-32 can perform more functions: harmonic analysis, 8 digital signal inputs, 4 programmable relay outputs, 4 programmable analog outputs (0-5V or 4-20mA), data storage, Profibus communication, Ethernet networking capabilities.

Description

Functions
ItemDescription
Main  unitReal-time measurementPhase Voltage     Phase Voltage, average phase Voltage
Line VoltageLine Voltage, average line Voltage
CurrentPhase Current, average phase Current, zero sequence Current
Active PowerPhase active Power, 3 phase active total Power
Reactive PowerPhase reactive Power, 3 phase reactive total Power
Apparent PowerPhase apparent Power, 3 phase apparent total Power
Power 4 quadrantPower 4 quadrant
FrequencySystem frequency
Power FactorPhase Power factor, 3 phase total Power factor
Demand statisticDemand3 phase active/reactive demand Power, demand apparent Power
Energy ReadingActive energyImported, exported and net active energy, 1 channel active  energy pulse output
Reactive energyImported, exported and net reactive energy, 1 channel reactive energy pulse output
Multi tariff billingMulti tariff setup
Time displayReal time displayYear/month/day/hour/minute/second
Data communicationRS-485 communication1 Modbus-RTU protocol
Optional  ModuleRemote signal input module8 channelsStatus detection, SOE event record
Relay output module4 channels programmable overlimit/underlimit alarmProgrammable over/under limit value for real time measurement, Volt- age/Current unbalanced ratio, demand value, harmonics, remote signal. The overlimit /underlimit command can be read thru com. Port.
Analog output module4 channels programmable4-20mA or 0-5V
Data storage moduleStorage capacity:2GBStore real time measured value in cycle, Voltage/Current unbalanced ratio, demand value, harmonics, and remote signal.
Harmonic analysis moduleTotal harmonic distortion for Voltage/Current3 phase, single phase, neutral line
Even/odd harmonic distortionHarmonic distortion (2nd to 63rd)
Fundermental Voltage / CurrentMagnitude,phase angle
Fundermental active/reactive powerMagnitude Phase angle
Harmonics, individual 
Current K factor 
Profibus communication module1channelProfibus-DP protocol
Ethernet networking communication module1channel10M/100M adaptable
TCP/IP protocol
Specification

Accuracy:

ParametersDisplayDirectionAccuracy
Voltage0~9999kV Class0.2
Current0~9999kA Class0.2
Power factor-1~+1DirectionalClass 1
Frequency45~65Hz 0.01Hz
Active Power-9999~9999MwDirectionalClass0.5
Reactive Power-9999~9999MVArDirectionalClass0.5
Apparent Power0~9999MVA Class0.5
Active Demand-9999~9999MW Class 1
Reactive Demand-9999~9999MVAr Class 1
Active Energy0~9999999.99MWhDirectionalClass 1
Reactive Energy0~9999999.99MVArhDirectionalClass 2
Phase Angle0.0°~359.9°DirectionalClass 2
Current total harmonic %0~100% Class 2
Voltage total harmonic %0~100% Class 2

Technical Specification:

Current Input
Input Current:0~5A   (Current value can be set up)
Measurement scope:0.5%~120%In
Overload capacity:2 X rated continuously,100A/1s non continuously
Power consumption:≤0.2VA per phase
Voltage Input
Input Voltage:0~400VAC (L-N),0~693VAC(L-L)(Voltage value can be set up)
System frequency:45~65Hz
Measurement scope:3%~120%Un
Overload Capacity:2 X rated continuous, 2500V/1s non continuous
Power consumption:≤0.5VA per phase
Switch Status (optional)
Input Channels:8 channels
Input Type:Dry contact
Isolated Voltage:                                                          2500VAC
Relay Output (optional)
Output Channels4 channels programmable
Output TypeMechanic contact, constant on output
Contact Capacity5A/250VAC
Analog Output (optional)
No. of outputs4 channels programmable
Output signal4~20mA or 0~5V
Response time≤400ms
Pulse Output (standard)
No. of outputs2 channels(active/reactive energy each)
Serial com. Port (standard)
No. of outputs1 RS-485 port
Communication protocolModbus-RTU protocol
Baud rate2400、4800、9600、19200、38400 bps
Profibus com. Module (optional)
No. of Channels1channel
Communication protocolProfibus-DP  protocol
Ethernet networking Module (optional)
No. of outputs1 channel 10M/100M adaptive
Communication protocolTCP/IP  protocol

Other Parameters:

Auxiliary Power85~265VAC/DC
Display moduleLCD display luminosity can be adjusted       
Temp. drifting factor<100PPM/℃
Withstand Voltage(input against output )2500V/1min
Total power consumption<8VA
Operation temperature-20℃~60℃
Storage temperature-40℃~85℃
Operation humidity5~95%RH
Pollution Class2 Class
Material of housingFlammability acc.  To UL94V0
Main unit96 x 96 x 86mm
Dimensional Size: Main unit+ module96 x 96 x 122mm
Installation Size:91 x 91mm

 

 

 

Customers also viewed: