CM-60 series protection controllers are designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. CM-60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

CM-60 products portfolio: standard CM-60-1S and CM-60-3S, popular CM-60-2M and integrated CM-60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

Description

Features
  • Variety of product portfolio to suit customers' needs
  • Recording function to record the instant data before and after the faults for fault analysis purpose
  • Flexible protection functions configuration to ensure the safe and continuous production
  • Automatic software and hardware inspection to increase the stability and reliability
  • Remote or local operation on parameters setup, motor start, stop, and reset
  • Detection on the motor start status automatically to avoid malfunction
  • Configured with large size LCD panel for on-site operation (optional)
Specification

Input (CM-60-2P)
Input Current: 1A, 6.3A,25A, 100A, 250A,500A, 800A

Input Voltage: 380VAC/50Hz
Remote digital signal input: 11 channels (dry contact)
Input (CM-60-2M)
Input Current: 1A, 5A,6.3A, 25A, 50A, 100A,160A, 200A, 250A

Input Voltage: 380VAC/50Hz
Remote digital signal input: 7 channels (220VAC)
Input (CM-60-1S)
Input Current: 5A

Remote digital signal input: 1 channel (dry contact)
Input (CM-60-3S)
Input Current: 1A, 5A,6.3A, 25A, 50A, 100A,160A, 200A, 250A
Remote digital signal input: 1 channel (dry contact)

Output (CM-60-2P)
RS-485 output: 2 channels
Analog output: 2 channels (4-20mA or 0-5V)
Relay output: 6 channels (dry contact)
Contact capacity of control output relay: 10A/250VAC
Contact capacity of alarm output relay: 5A/250VAC
Output (CM-60-2M)
RS-485 output: 1 channel

Analog output: 1 channel (4-20mA or 0-5V)
Relay output: 4 channels (dry contact)
Contact capacity of control output relay: 10A/250VAC
Output (CM-60-1S & CM-60-3S)
RS-485 output: 1 channel
Analog output: CM-60-1S, 1 channel (4-20mA or 0-5V)
Relay output: 2 channels (dry contact)
Contact capacity of control output relay: 10A/250VAC
Contact capacity of alarm output relay: 10A/250VAC

Measurement Record (CM-60-2P)
Accuracy: U, I, F class 0.5
Accuracy: cosΦ, P, Q class 1
Accuracy: Ep class 2
Accumulated operating time on record (Max.): 65535 hours
Measurement Record (CM-60-2M)
Accuracy: U, I, F class 0.5

Accuracy: cosΦ, P, Q class 1
Accuracy: Ep class 2
Accumulated operating time on record (Max.): 65535 hours.
Measurement Record (CM-60-1S & CM-60-3S)
Accuracy: I, class 0.5
Accumulated operating time on record (Max.): 9999days

Size & Weight: (CM-60-2P)
Installation (CM-60-2P): 35mm Din rail, with 4 M4 bolts to support
Installation (CT): with 4 M4 bolts to support
Dimensional size (CM-60-2P): 82mmX100mmX106mm
Operating panel size: 76mmX61mmX28mm
Weight: 450g(not including CT)
Remark: The size and weight of CT is decided by input current.
Size & Weight: (CM-60-2M)
Installation: 35mm Din rail, with 3 M4 bolts to support

Dimensional size: 75mmX80mmX103mm (<100A )
Dimensional Size: 75mmX102mmX140mm (100A-250A)
Operating panel size: 76mmX61mmX17mm
Weight: 450g ( 100A )
Weight: 560g ( 250A )
Size & Weight: (CM-60-1S & CM-60-3S)
Installation: Panel mounting
Dimensional size: 96mmX48mmX76mm
Installation size: 94mmX46mm
Weight: 450g

Environment
Auxiliary power supply: 85~265VAC/DC

Total power consumption:<5VA(CM-60-2M)
Operation temperature: -20℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Operation humidity: <90%RH
Storage humidity: <95%RH

Restart function after Voltage Fluctuation (CM-60-2P & CM-60-2M)
Voltage fluctuation allowing time: 0.1-25.5S
Restart delay time: 0.1-25.5S
Time adjustment step: 0.1S
Lower Voltage setup scope:80%-89%Ue

 

 

Protection Function
FunctionStatusItemContentCM-60-1SCM-60-3SCM-60-2MCM-60-2P
Overtime start protectionProgrammableAllowed startup time0-80sYesYesYesYes
Protection method2
Short circuit protectionProgrammableFault setting range4-12leYesYesYesYes
Execution delay time0.1-0.5s
Protection method0, 2
Locked rotor protectionProgrammableFault setting range200-950%leYesYesYesYes
Warning setting range150-255%le
Execution delay time0.1-25.5s
Protection method0, 1, 2, 4
Underload protectionProgrammableSetting range20-95%leYesYesYesYes
Execution delay time0.1-60s
Protection method0, 1, 2, 3
Overload protectionProgrammableSetting range105-150%leYesYesYesYes
Execution delay time0.1-250s
Protection method0, 1, 2, 3, 4
Thermal by overloadMustSetting range1-105%θbYesYesYesYes
Protection method4
tE time protection (Increased Safty Motor)ProgrammabletE time1.0-15sYesYesYesYes
Protection method4
Unbalance protection (phase failure)ProgrammableSetting range10%-60%YesYesYesYes
Execution delay time0.1-30s
Protection method0, 2, 4
Over power protectionProgrammableSetting range101-120%Pe  YesYes
Execution delay time0.1-200s
Protection method0, 1, 2, 3
Under power protectionProgrammableSetting range30-80%Pe  YesYes
Execution delay time0.1-200s
Protection method0, 1, 2, 3
Over power factor protectionProgrammableSetting range0.01-1.00  YesYes
Execution delay time0.1-25.5s
Protection method0, 1, 2, 3
Under power factor protectionProgrammableSetting range0.01-1.00  YesYes
Execution delay time0.1-25.5s
Protection method0, 1, 2, 3
Phase reversal protectionPorgrammableExecution delay time0.1-25.5s  YesYes
Protection method0, 2
Under voltage protectionProgrammableSetting range45-95%Ue  YesYes
Execution delay time0.1-200s
Protection method0, 1, 2, 3
Over voltage protectionProgrammableSetting range101-120%Ue  YesYes
Execution delay time0.1-200s
Protection method0, 1, 2, 3
Leakage Current protectionProgrammableSetting range10-500mA  YesYes
Execution delay time0.1-5s
Protection method0, 1, 2
Overheat protectionProgrammableExecution delay time0.5s   Yes
Protection method0, 2
Interlock protectionProgrammableExecution delay time0.1-60sYesYesYesYes
Protection method2
Connection to ground protctionProgrammableSetting range10-100%IeYesYesYesYes
Execution delay time0.1-5s
Protection method0, 2

 

 M60-1SM60-3SM60-2MM60-2P
Control function
Direct start  YesYes
Reversing start         Yes
Y-△Start   Yes
Lower Voltage start   Yes
Restart motors caused by Voltage fluctuation       YesYes
Emergency fault output  YesYes
Local/remote command of start, stop  YesYes
Measurement function
Operating CurrentYesYesYesYes
Unbalanced Current ratioYesYesYesYes
Voltage, frequency, power, power factor,leakage current     YesYes
No. of contact executions  YesYes
Status of contacts  YesYes
Record Function
Latest 10 start/stop record  ClockClock
Latest 10 alarm record  No clockNo clockClockClock
Latest 10 trip recordNo clockNo clockClockClock
Latest 10 restart record caused by Voltage fluctuation  ClockClock
Max. and min. parameters records in the protection executionYesYesYesYes
Accumulated operating time of motor  YesYesYesYes
Communication Function
RS-485 com. PortYesYesYesYes
Modbus protocol   YesYesYesYes
Profibus protocol     Yes